Corrosion processes in cooling towers
Corrosion testing was performed on structural steel of a cooling tower in the environment of cooling water containing ammonium sulfates and ammonium chloride. The test were performed using gravimetric and electrochemical methods with the application of a potentiostat. The analyses clearly showed th...
Main Authors: | , |
---|---|
Format: | Article |
Language: | English |
Published: |
Lublin University of Technology
2013-09-01
|
Series: | Budownictwo i Architektura |
Subjects: | |
Online Access: | https://ph.pollub.pl/index.php/bia/article/view/2036 |
Summary: | Corrosion testing was performed on structural steel of a cooling tower in the environment of cooling water containing ammonium sulfates and ammonium chloride. The test were performed using gravimetric and electrochemical methods with the application of a potentiostat. The analyses clearly showed that the corrosion rate is higher in solutions that contain ammonium sulfate and that the S235JRG2 steel exhibits higher corrosion resistance in this environment.
|
---|---|
ISSN: | 1899-0665 2544-3275 |