The study on the Mal-operation of the transformer current differential protection during external faults cause by CT saturation
This paper analyses the unusual mal-operation of the differential protection for transformer current differential protection during the external fault. The mal-operation reason is researched in detail, based on the mathematical analysis, the simulation, and the field recorded fault data analysis. It...
Main Authors: | Wu Jianhong, Qi Xuanwei, Song Wang, Cao Wenbin, He Jun, Mao Lan |
---|---|
Format: | Article |
Language: | English |
Published: |
EDP Sciences
2021-01-01
|
Series: | E3S Web of Conferences |
Subjects: | |
Online Access: | https://www.e3s-conferences.org/articles/e3sconf/pdf/2021/36/e3sconf_aepee2021_02016.pdf |