Parametric Analysis of Energy Saving of DCBL Motor in the Application of Variable Air Volume Air-conditioning Systems
碩士 === 國立臺北科技大學 === 冷凍空調工程系所 === 93 === Owing to limited energy resources and conscience in environment protection, there is a rising trend on energy saving. Besides chiller efficiency, high potential energy saving in air-conditioning can be found in improving the efficiency of fan systems. Signific...
Main Authors: | , |
---|---|
Other Authors: | |
Format: | Others |
Language: | zh-TW |
Published: |
2005
|
Online Access: | http://ndltd.ncl.edu.tw/handle/9ah38e |
id |
ndltd-TW-093TIT05703007 |
---|---|
record_format |
oai_dc |
spelling |
ndltd-TW-093TIT057030072019-05-31T03:35:54Z http://ndltd.ncl.edu.tw/handle/9ah38e Parametric Analysis of Energy Saving of DCBL Motor in the Application of Variable Air Volume Air-conditioning Systems 直流無刷馬達應用於空調變風量節能之參數分析 Daniel(I Te) Chou 周依德 碩士 國立臺北科技大學 冷凍空調工程系所 93 Owing to limited energy resources and conscience in environment protection, there is a rising trend on energy saving. Besides chiller efficiency, high potential energy saving in air-conditioning can be found in improving the efficiency of fan systems. Significant saving in electric energy can be realized by reducing the fan motor speed when indoor cooling load decreased. The thesis conducts a study on the energy saving potential of Direct Current Brushless (DCBL) motor. High efficiency, high torque, and compactness are the characteristics of DCBL motor. It is used to control the air volume according to different cooling load. An experiment was setup with a newly developed fan coil unit. The experimental setup simulates the actual applications through controllable heating as the cooling load. The operation variation of DCBL motor applying to variable air volume under different temperature conditions were tested in the experiments. The variations of electric voltage, current, power consumption, frequency, and the wave pattern were measured and analyzed. The variations of these parameters are used to show the energy saving potential of DCBL motor fan coil. The tests were used to verify that DCBL motor can respond well to the cooling capacity of a HVAC system under normal operation. It can reduce the indoor temperature to comfort zone within short period of time and can also maintain it well. It was found that DCBL motor variable air volume system used only 30% of input power compare with that of permanent split capacitor motor at low cooling load. The test results prove that the high efficiency operation of this technology can decrease the power consumption of air-conditioning significantly. Yew-Khoy Chuah 蔡尤溪 2005 學位論文 ; thesis 100 zh-TW |
collection |
NDLTD |
language |
zh-TW |
format |
Others
|
sources |
NDLTD |
description |
碩士 === 國立臺北科技大學 === 冷凍空調工程系所 === 93 === Owing to limited energy resources and conscience in environment protection, there is a rising trend on energy saving. Besides chiller efficiency, high potential energy saving in air-conditioning can be found in improving the efficiency of fan systems. Significant saving in electric energy can be realized by reducing the fan motor speed when indoor cooling load decreased.
The thesis conducts a study on the energy saving potential of Direct Current Brushless (DCBL) motor. High efficiency, high torque, and compactness are the characteristics of DCBL motor. It is used to control the air volume according to different cooling load.
An experiment was setup with a newly developed fan coil unit. The experimental setup simulates the actual applications through controllable heating as the cooling load. The operation variation of DCBL motor applying to variable air volume under different temperature conditions were tested in the experiments. The variations of electric voltage, current, power consumption, frequency, and the wave pattern were measured and analyzed. The variations of these parameters are used to show the energy saving potential of DCBL motor fan coil.
The tests were used to verify that DCBL motor can respond well to the cooling capacity of a HVAC system under normal operation. It can reduce the indoor temperature to comfort zone within short period of time and can also maintain it well. It was found that DCBL motor variable air volume system used only 30% of input power compare with that of permanent split capacitor motor at low cooling load. The test results prove that the high efficiency operation of this technology can decrease the power consumption of air-conditioning significantly.
|
author2 |
Yew-Khoy Chuah |
author_facet |
Yew-Khoy Chuah Daniel(I Te) Chou 周依德 |
author |
Daniel(I Te) Chou 周依德 |
spellingShingle |
Daniel(I Te) Chou 周依德 Parametric Analysis of Energy Saving of DCBL Motor in the Application of Variable Air Volume Air-conditioning Systems |
author_sort |
Daniel(I Te) Chou |
title |
Parametric Analysis of Energy Saving of DCBL Motor in the Application of Variable Air Volume Air-conditioning Systems |
title_short |
Parametric Analysis of Energy Saving of DCBL Motor in the Application of Variable Air Volume Air-conditioning Systems |
title_full |
Parametric Analysis of Energy Saving of DCBL Motor in the Application of Variable Air Volume Air-conditioning Systems |
title_fullStr |
Parametric Analysis of Energy Saving of DCBL Motor in the Application of Variable Air Volume Air-conditioning Systems |
title_full_unstemmed |
Parametric Analysis of Energy Saving of DCBL Motor in the Application of Variable Air Volume Air-conditioning Systems |
title_sort |
parametric analysis of energy saving of dcbl motor in the application of variable air volume air-conditioning systems |
publishDate |
2005 |
url |
http://ndltd.ncl.edu.tw/handle/9ah38e |
work_keys_str_mv |
AT danielitechou parametricanalysisofenergysavingofdcblmotorintheapplicationofvariableairvolumeairconditioningsystems AT zhōuyīdé parametricanalysisofenergysavingofdcblmotorintheapplicationofvariableairvolumeairconditioningsystems AT danielitechou zhíliúwúshuāmǎdáyīngyòngyúkōngdiàobiànfēngliàngjiénéngzhīcānshùfēnxī AT zhōuyīdé zhíliúwúshuāmǎdáyīngyòngyúkōngdiàobiànfēngliàngjiénéngzhīcānshùfēnxī |
_version_ |
1719197231260631040 |