Use moisture wicking fiber evapotranspiration to enhance performance of R-410A split air conditioner

碩士 === 國立臺灣師範大學 === 工業教育學系 === 105 === This study aimed to enhance the performance of R-410A split air conditioner by using moisture transferring and quick drying textiles (MTQDT). The main method is decreased compressor temperature through evaporative cooling effect of the MTQDT and achieved the pu...

Full description

Bibliographic Details
Main Authors: Chen, Wei-Han, 陳韋翰
Other Authors: Mo, Huai-En
Format: Others
Language:zh-TW
Published: 2017
Online Access:http://ndltd.ncl.edu.tw/handle/mqrf7s
Description
Summary:碩士 === 國立臺灣師範大學 === 工業教育學系 === 105 === This study aimed to enhance the performance of R-410A split air conditioner by using moisture transferring and quick drying textiles (MTQDT). The main method is decreased compressor temperature through evaporative cooling effect of the MTQDT and achieved the purpose of this study. We went on performance measurement using the same indoor load and the different ambient temperature (30±1°C, 35±1°C and 40±1°C). The results show that the MTQDT can successfully apply in a R410A split air conditioner. In the ambient temperature of 30°C, 35°C and 40°C, it prove that the compressor outlet temperature is reduced by 7.5%, 7.4% and 6.2%, the COP is improved by 20.68, 18.3% and 17.69%, and the EER is raised by 4.39%, 6.42% and 4.87%.