[en] DYNAMIC AGGREGATION OF DUAL-INPUT POWER SYSTEM STABILIZER MODELS TO CALCULATE DYNAMIC EQUIVALENTS
[pt] Esta dissertação trata do problema da agregação dinâmica de modelos de estabilizadores com dupla entrada, aplicados em reguladores de tensão de unidades geradoras coerentes, visando o cálculo de equivalentes dinâmicos precisos para estudos de estabilidade transitória de sistemas de energia...
Main Author: | |
---|---|
Other Authors: | |
Language: | pt |
Published: |
MAXWELL
2003
|
Subjects: | |
Online Access: | https://www.maxwell.vrac.puc-rio.br/Busca_etds.php?strSecao=resultado&nrSeq=3278@1 https://www.maxwell.vrac.puc-rio.br/Busca_etds.php?strSecao=resultado&nrSeq=3278@2 http://doi.org/10.17771/PUCRio.acad.3278 |
id |
ndltd-puc-rio.br-oai-MAXWELL.puc-rio.br-3278 |
---|---|
record_format |
oai_dc |
collection |
NDLTD |
language |
pt |
sources |
NDLTD |
topic |
[pt] ESTABILIDADE TRANSITORIA [en] TRANSIENT STABILITY [pt] EQUIVALENTES DINAMICOS [en] DYNAMIC EQUIVALENTS [pt] GERADORES COERENTES [en] COHERENT GENERATORS [pt] AGREGACAO DINAMICA [en] DYNAMIC AGGREGATION [pt] SISTEMAS DE EXCITACAO [en] EXCITATION SYSTEMS [pt] ESTABILIZADORES [en] POWER SYSTEM STABILIZERS |
spellingShingle |
[pt] ESTABILIDADE TRANSITORIA [en] TRANSIENT STABILITY [pt] EQUIVALENTES DINAMICOS [en] DYNAMIC EQUIVALENTS [pt] GERADORES COERENTES [en] COHERENT GENERATORS [pt] AGREGACAO DINAMICA [en] DYNAMIC AGGREGATION [pt] SISTEMAS DE EXCITACAO [en] EXCITATION SYSTEMS [pt] ESTABILIZADORES [en] POWER SYSTEM STABILIZERS MARCOS ANTONIO ALBUQUERQUE [en] DYNAMIC AGGREGATION OF DUAL-INPUT POWER SYSTEM STABILIZER MODELS TO CALCULATE DYNAMIC EQUIVALENTS |
description |
[pt] Esta dissertação trata do problema da agregação dinâmica de
modelos de estabilizadores com dupla entrada, aplicados em
reguladores de tensão de unidades geradoras coerentes,
visando o cálculo de equivalentes dinâmicos precisos para
estudos de estabilidade transitória de sistemas de energia
elétrica. A metodologia utilizada para o cálculo de
equivalentes dinâmicos é baseada em coerência de geradores,
e apresenta três etapas básicas: a identificação de
unidades geradoras coerentes, a redução estática da rede
externa, e a agregação dinâmica dos geradores de cada grupo
formado. A agregação dinâmica de um grupo de unidades
geradoras coerentes permite a formação de uma ou mais
unidades geradoras equivalentes. Haverá um modelo
equivalente para cada componente da unidade geradora, ou
seja, modelos equivalentes de máquina síncrona, sistema de
excitação, estabilizador, turbina e regulador de
velocidade. O ajuste numérico dos parâmetros lineares da
função de transferência equivalente é feito pelo método de
Levenberg-Marquardt, de modo a minimizar o erro entre a
resposta em freqüência desta função e a da função de
transferência agregada, que representa a soma das funções
de transferência individuais das unidades de cada
grupo. Isto caracteriza um problema de otimização
multivariável. As respostas em freqüência são apresentadas
em diagramas de Bode (módulo e fase). A avaliação do
desempenho dinâmico dos equivalentes é feita no sistema
teste New England, comparando-se as curvas de oscilação dos
geradores do sistema interno obtidas em simulações com a
rede completa e com o equivalente. Os modelos de
estabilizadores com dupla entrada utilizados são do banco
de dados do sistema elétrico brasileiro.
=== [en] This dissertation deals with the problem of dynamic
aggregation of dualinput stabilizer models applied on
voltage regulators of coherent generating units
to calculate dynamic equivalents for power system transient
stability studies. The methodology used for the calculation
of coherency-based dynamic equivalents has three basic
steps: the identification of the coherent groups of
generating units, the network reduction and the dynamic
aggregation of coherent generator models. The dynamic
aggregation of a group of coherent generating units
attached to a common busbar consists of the representation
of this group by one or more equivalent generating units.
There will be an equivalent model for each component of the
generating unit, i.e., an equivalent model for the
synchronous machine, other one for the excitation system,
and so on. The linear parameters of the equivalent transfer
function are numerically adjusted to match the frequency
response of the corresponding aggregated transfer function
which represents the sum of the individual transfer
functions for each coherent group. This characterises a
multivariable optimization problem. The frequency responses
are presented in Bode diagrams (magnitude and phase). The
dynamic equivalents are evaluated in the New England
system. The swing curves of the internal system generators
obtained with the complete system are compared with those
obtained with the equivalent system. The dual-input power
system stabilizer models considered in this work are in the
Brazilian system stability database. |
author2 |
EDUARDO JOSE SIQUEIRA PIRES DE SOUZA |
author_facet |
EDUARDO JOSE SIQUEIRA PIRES DE SOUZA MARCOS ANTONIO ALBUQUERQUE |
author |
MARCOS ANTONIO ALBUQUERQUE |
author_sort |
MARCOS ANTONIO ALBUQUERQUE |
title |
[en] DYNAMIC AGGREGATION OF DUAL-INPUT POWER SYSTEM STABILIZER MODELS TO CALCULATE DYNAMIC EQUIVALENTS |
title_short |
[en] DYNAMIC AGGREGATION OF DUAL-INPUT POWER SYSTEM STABILIZER MODELS TO CALCULATE DYNAMIC EQUIVALENTS |
title_full |
[en] DYNAMIC AGGREGATION OF DUAL-INPUT POWER SYSTEM STABILIZER MODELS TO CALCULATE DYNAMIC EQUIVALENTS |
title_fullStr |
[en] DYNAMIC AGGREGATION OF DUAL-INPUT POWER SYSTEM STABILIZER MODELS TO CALCULATE DYNAMIC EQUIVALENTS |
title_full_unstemmed |
[en] DYNAMIC AGGREGATION OF DUAL-INPUT POWER SYSTEM STABILIZER MODELS TO CALCULATE DYNAMIC EQUIVALENTS |
title_sort |
[en] dynamic aggregation of dual-input power system stabilizer models to calculate dynamic equivalents |
publisher |
MAXWELL |
publishDate |
2003 |
url |
https://www.maxwell.vrac.puc-rio.br/Busca_etds.php?strSecao=resultado&nrSeq=3278@1 https://www.maxwell.vrac.puc-rio.br/Busca_etds.php?strSecao=resultado&nrSeq=3278@2 http://doi.org/10.17771/PUCRio.acad.3278 |
work_keys_str_mv |
AT marcosantonioalbuquerque endynamicaggregationofdualinputpowersystemstabilizermodelstocalculatedynamicequivalents AT marcosantonioalbuquerque ptagregacaodinamicademodelosdeestabilizadorescomduplaentradaparaocalculodeequivalentesdinamicos |
_version_ |
1718532863310168064 |
spelling |
ndltd-puc-rio.br-oai-MAXWELL.puc-rio.br-32782017-09-15T04:08:12Z[en] DYNAMIC AGGREGATION OF DUAL-INPUT POWER SYSTEM STABILIZER MODELS TO CALCULATE DYNAMIC EQUIVALENTS [pt] AGREGAÇÃO DINÂMICA DE MODELOS DE ESTABILIZADORES COM DUPLA ENTRADA PARA O CÁLCULO DE EQUIVALENTES DINÂMICOS MARCOS ANTONIO ALBUQUERQUE[pt] ESTABILIDADE TRANSITORIA[en] TRANSIENT STABILITY[pt] EQUIVALENTES DINAMICOS[en] DYNAMIC EQUIVALENTS[pt] GERADORES COERENTES[en] COHERENT GENERATORS[pt] AGREGACAO DINAMICA[en] DYNAMIC AGGREGATION[pt] SISTEMAS DE EXCITACAO[en] EXCITATION SYSTEMS[pt] ESTABILIZADORES[en] POWER SYSTEM STABILIZERS[pt] Esta dissertação trata do problema da agregação dinâmica de modelos de estabilizadores com dupla entrada, aplicados em reguladores de tensão de unidades geradoras coerentes, visando o cálculo de equivalentes dinâmicos precisos para estudos de estabilidade transitória de sistemas de energia elétrica. A metodologia utilizada para o cálculo de equivalentes dinâmicos é baseada em coerência de geradores, e apresenta três etapas básicas: a identificação de unidades geradoras coerentes, a redução estática da rede externa, e a agregação dinâmica dos geradores de cada grupo formado. A agregação dinâmica de um grupo de unidades geradoras coerentes permite a formação de uma ou mais unidades geradoras equivalentes. Haverá um modelo equivalente para cada componente da unidade geradora, ou seja, modelos equivalentes de máquina síncrona, sistema de excitação, estabilizador, turbina e regulador de velocidade. O ajuste numérico dos parâmetros lineares da função de transferência equivalente é feito pelo método de Levenberg-Marquardt, de modo a minimizar o erro entre a resposta em freqüência desta função e a da função de transferência agregada, que representa a soma das funções de transferência individuais das unidades de cada grupo. Isto caracteriza um problema de otimização multivariável. As respostas em freqüência são apresentadas em diagramas de Bode (módulo e fase). A avaliação do desempenho dinâmico dos equivalentes é feita no sistema teste New England, comparando-se as curvas de oscilação dos geradores do sistema interno obtidas em simulações com a rede completa e com o equivalente. Os modelos de estabilizadores com dupla entrada utilizados são do banco de dados do sistema elétrico brasileiro. [en] This dissertation deals with the problem of dynamic aggregation of dualinput stabilizer models applied on voltage regulators of coherent generating units to calculate dynamic equivalents for power system transient stability studies. The methodology used for the calculation of coherency-based dynamic equivalents has three basic steps: the identification of the coherent groups of generating units, the network reduction and the dynamic aggregation of coherent generator models. The dynamic aggregation of a group of coherent generating units attached to a common busbar consists of the representation of this group by one or more equivalent generating units. There will be an equivalent model for each component of the generating unit, i.e., an equivalent model for the synchronous machine, other one for the excitation system, and so on. The linear parameters of the equivalent transfer function are numerically adjusted to match the frequency response of the corresponding aggregated transfer function which represents the sum of the individual transfer functions for each coherent group. This characterises a multivariable optimization problem. The frequency responses are presented in Bode diagrams (magnitude and phase). The dynamic equivalents are evaluated in the New England system. The swing curves of the internal system generators obtained with the complete system are compared with those obtained with the equivalent system. The dual-input power system stabilizer models considered in this work are in the Brazilian system stability database.MAXWELLEDUARDO JOSE SIQUEIRA PIRES DE SOUZA2003-02-25TEXTOhttps://www.maxwell.vrac.puc-rio.br/Busca_etds.php?strSecao=resultado&nrSeq=3278@1https://www.maxwell.vrac.puc-rio.br/Busca_etds.php?strSecao=resultado&nrSeq=3278@2http://doi.org/10.17771/PUCRio.acad.3278pt |